Description of FA100
FA100 is an aspirating smoke detector equipped with two removable and independent sampling chambers.
The device is equipped with an aspirator, common to both detector modules, which draws the air from the rooms monitored through two distinct piping networks.
The product is supplied with only one detection module; a second one can be purchased separately.
Each of the detector modules can be configured independently in class A, B or C (see “Detection Classes”) and can support a maximum number of sampling holes equal to 8, 18 and 51 respectively.
The detector modules are based on a dual light technology that uses two distinct light sources (infrared and blue) capable of evaluating the dimensions of the aspirated particulate and of providing a prompt response in outbreaks of fire as well as a high rejection of false alarms caused by dust or mists.
Each of the detector modules is capable of measuring the flow rate of the aspirated air and of signalling a fault if this deviates from the value set when activating the system (clogged sampling holes or breaks in the sampling duct).
FA100 can be connected to Inim Electronics addressable fire control panels by connecting it directly to the loop (the power supply voltage must be supplied separately) thus transferring all the signals and controls to the control panel, or it can be connected to any conventional control panel thanks to its relay outputs and I/O terminals.
Main features
-
2 detector modules with independent smoke and flow detectors
-
optical smoke detection with dual light technology: infrared and blue
-
Classification A, B and C in accordance with EN 54-20
-
programmable sensitivity from 235 to 20000 · 10-5 dB/m
-
one detection module supplied and one optional
-
single aspiration fan
-
6 dual switching relays, free contacts (not certified in accordance with EN 54-18)
-
4 programmable inputs / open collector outputs (not certified in accordance with EN 54-18)
-
optional FA100-WIFI Wi-Fi module for communication with a PC for programming and diagnostics
-
LCD graphic display
Functions
-
Connection to the loop of an addressable analogue switch of the Inim Electronics
-
Connection to a conventional control panel (via a fault relay, an alarm relay, a programmable input and suitable balancing resistors)
-
Levels of detection for warning and smoke alarm programmable and independent for each aspiration pipe
-
Automatic rearm: if enabled, the warning and alarm status are reset when the smoke level drops below the programmed thresholds
-
Non-volatile memory for the recording of the trend of the smoke level, air flow and air temperature for each individual aspiration pipe
-
Memory storage capacity for at least two months of detection data with 1-minute sampling
-
Management of summer/winter time